|
Issue No. 1 |
|
Current News --
Fall 2008
Code Alert: Georgia, 30 July 2008 |
|
The following
information was just released by NEMA
http://www.nema.org/stds/fieldreps/codealerts/20080730ga.cfm
|
|
On July 24, 2008,
the Georgia State Codes Advisory Committee voted unanimously to
recommend adoption of the 2008 edition of the National
Electrical Code® with the following amendments: |
|
|
|
1) Delete
Section 406.11, ‘Tamper-Resistant Receptacles in Dwelling Units’
without substitution. |
|
|
|
406.11
Tamper-Resistant Receptacles in Dwelling Units.
This section of
the 2008 NEC currently reads, “In all areas specified in 210.52,
all 125-volt, 15- and 20-ampere receptacles shall be listed
tamper-resistant receptacles.” |
|
|
|
2) Revise
Item (2) of Subsection (A) ‘Dwelling Units’ of Section 210.8,
‘Ground-Fault Circuit Interrupter Protection for Personnel’ to
add exception as follows: |
|
|
|
Exception No. 1 to
(2): Receptacles supplying an overhead garage door operator
shall not be required to have ground-fault circuit-interrupter
protection. |
|
|
|
Exception No. 2 to
(2): A single receptacle or a duplex receptacle for two
appliances located within dedicated space for each appliance
that, in normal use, is not easily moved from one place to
another and that is cord-and-plug connected in accordance with
400.7(A)(6), (A)(7), or (A)(8). Receptacles installed under the
exceptions to 210.8(A)(5) shall not be considered as meeting the
requirements of 210.52(G). All non-GFCI protected receptacles
shall be clearly marked. |
|
|
|
3) Revise
Item (5)(a) of Subsection (B) ‘Not Covered’ of Section 90.2
‘Scope’ as follows: |
|
|
|
b. Are located in
legally established easements, or rights-of-way,
or by other agreements either designated by or recognized
by public service commissions, utility commissions, or other
regulatory agencies having jurisdiction for such installations,
or |
|
|
|
4) Revise
210.12(B) ‘Dwelling Units’ of 210.12 on a time dated amendment
as follows: |
|
|
|
Delete 2008 NEC,
Section 210.8(B)
All 120-volt,
single phase, 15- and 20-ampere branch circuits supplying
outlets installed in dwelling unit family rooms, dining rooms,
living rooms, parlors, libraries, dens, bedrooms, sunrooms,
recreation rooms, closets, hallways, or similar rooms or areas
shall be protected by a listed arc-fault circuit interrupter,
combination-type, installed to provide protection of the branch
circuit. |
|
|
|
Add 2005 NEC
language from Section 210.8(B)
All 120-volt,
single phase, 15- and 20-ampere branch circuits supplying
outlets installed in dwelling unit bedrooms shall be protected
by a listed arc-fault circuit interrupter, combination type
installed to provide protection of the branch circuit. |
|
|
|
The provisions of
210.12(B) of the 2005 edition of the National Electrical Code®
shall be permitted to be used to meet the requirements of
210.12(B) of the 2008 edition of the National Electrical Code®
until January 1, 2010. |
|
|
|
The first three
recommended amendments 1) ‘Tamper Resistant Receptacles in
Dwelling Units’, 2) ‘Ground-Fault Circuit Interrupter Protection
for Personnel’, and 3) ‘Not Covered’ of Section 90.2 ‘Scope’
were suggested by a Task Force appointed by the Chairman of the
State Codes Advisory Committee (SCAC), William Duck, Building
Official from the City of Columbus, GA. Members of the Task
Force included: |
|
|
-
William Duck, Jr., Chairman - Building Official for
Columbus, GA – Code Enforcement Officials
|
-
Morgan Wheeler, Vice Chairman – Building Official for Walton
County – Code Enforcement Officials
|
-
Thomas J. Carty, Secretary – Building official for Peachtree
City – Code Enforcement Officials
|
-
Gregory Anderson – Building Official for Chatham County –
Code Enforcement Officials
|
-
Dwayne Garriss – State Fire Marshal’s Office – Georgia Fire
Safety Commissioner
|
-
Mr.
Iby George – Local Fire Officials
|
-
David Adams – Local Fire Officials
|
-
Windell Peters – AGL Resources - Commissioner of Community
Affairs
|
-
Tom
Collins - Industrialized Building Industry
|
-
William Lusk – General Contracting Industry
|
-
Rex
Pless – Structural Engineering Profession
|
-
Gregg Johnson – Mechanical Engineering Profession
|
-
James Vaseff – Architectural Engineering Professional
|
-
Danny Lundstrom – Electrical Engineering Profession
|
-
Roy
Dailey – Manufactured Homes Industry
|
-
Mike
Bean – Electrical Contracting Industry
|
-
Robert Magbee – Building Material Industry
|
-
William Guinade – Plumbing Contracting Industry
|
-
Barry Abernathy – Conditioned Air Contractors Industry
|
-
Tim
Williams – Home Building Contractors Industry
|
-
Paul
Tuggle – Human Resources Commissioner
|
|
|
|
The reasons given
by SCAC in supporting the recommended amendment deleting ‘Tamper
Resistant Receptacles in Dwelling Units’ were cost,
availability of product, the uncertainty of where the
receptacles would be required, requirements for receptacles in
areas not easily reached by children, and the question of
usability by older people. One SCAC building official member
stated he had been quoted a price of over $5 for a tamper
resistant receptacle at a home improvements store even though he
is one of the most electrically knowledgeable members of the
SCAC and had to have known he was pricing a hospital grade
tamper resistant receptacle and not a residential grad
receptacle. Even though each of these issues was thoroughly
answered by electrical industry representatives in attendance at
the meeting, SCAC officials approved the amendment on a raised
hand vote of 11-6. |
|
|
|
There was no
discussion of the second recommended amendment, Section 210.8,
‘Ground-Fault Circuit Interrupter Protection for Personnel’, to
add exceptions that would prohibit enforcement of GFCI
protection. The vote to support this amendment was a voice vote
of 16-1. |
|
|
|
There was no
discussion of the third recommended amendment, item (5)(a) of
Subsection (B) ‘Not Covered’ of Section 90.2 ‘Scope’, and only
one clarifying statement being offered by an audience member as
to the reason for the revision to the 2008 NEC that is amended
by this amendment. |
|
|
|
The fourth
amendment came from a motion on SCAC member Thomas Carty,
Building Official for Peachtree City, GA and current President
of the Georgia Building officials Association. It should be
noted that Mr. Carty is one of the more electrically
knowledgeable people on SCAC. It appeared the main issues
concerned the inability of Georgia electrical contractors and
their people to perform troubleshooting procedures where AFCI
protected devices trip for apparently unknown and unfound
reasons, and the cost of the devices which was as always greatly
inflated on estimates given by a home builder association’s
representative. The vote on this amendment was 12-5 in favor. |
|
|
|
In all very little
testimony came from the majority of the SCAC members with most
comments supporting the deletion of 406.11, the revisions to
210.8(A) Exceptions, and the hold placed on implementation of
the expansion of AFCI in dwelling units being lead by the SCAC
Code Enforcement Officials members, plus the DCA Commissioner’s
representative and the home builder’s representative. For the
most part except for one self-identified electrical contractor
and a representative of the Greater Atlanta’s Homebuilders
Association, the comments from the audience were in opposition
to the amendments with one Georgia building official speaking in
opposition to the amendments restricting AFCI and tamper
resistant receptacles. It was also interesting to note that
the State Fire Marshal’s office that has a member, Dwayne
Garriss, on this important committee, was not represented at
this SCAC meeting thus the State Fire Marshal’s Office seemed to
choose not to go on record concerning these important issues. |
|
|
|
This issue next
goes to a review hearing that is tentatively scheduled for
September 24, 2008 and then to the Georgia Department of
Community Affairs Board meeting scheduled for November 5, 2008
in Atlanta. |
|
|
|
Contact: John
Minick:
john.minick@nema.org |
|
|
|
J & W 2008 Fall Seminar Schedule |
|
|
|
NO. |
Date |
Location |
Facility |
Address |
Topic |
Inst |
|
1 |
9/11 |
Alma |
Satilla REMC |
Ga Hwy 32 E |
2008 NEC Motors - HVAC |
Carter |
|
2 |
9/16 |
Jackson |
Central Ga EMC |
923 S. Mulberry St. |
2008 NEC Motors - HVAC |
Allison |
|
3 |
9/18 |
Augusta |
Georgia Power |
2103 North Leg Rd |
2008 NEC Motors - HVAC |
Carter |
|
4 |
9/25 |
Rome |
Georgia Power |
800 Broad St |
2008 NEC Motors - HVAC |
Carter |
|
5 |
9/30 |
Athens |
UGA |
Dirftmire Eng Ct |
2008 NEC Motors - HVAC |
Allison |
|
6 |
10/14 |
Clarkesville |
Habersham EMC |
6135 Hwy 115 W |
2008 NEC Motors - HVAC |
Allison |
|
7 |
10/16 |
Statesboro |
Georgia Power |
111 Stockyard Dr |
2008 NEC Motors - HVAC |
Carter |
|
8 |
10/21 |
Snellville |
Walton EMC |
3645 Lenora Ch Rd |
2008 NEC Motors - HVAC |
Carter |
|
9 |
11/4 |
Douglasville |
GrayStone Power |
4040 Bankhead Hwy |
2008 NEC Motors - HVAC |
Allison |
|
10 |
11/16 |
Albany |
Mitchell EMC |
5807 Newton Road |
2008 NEC Motors - HVAC |
Allison |
|
11 |
TBA |
Savannah |
Georgia Power |
600 East Bay St |
2008 NEC Motors - HVAC |
Allison |
|
12 |
TBA |
Columbus |
Georgia Power |
3610 Gentian Blvd |
2008 NEC Motors - HVAC |
Carter |
|
|
|
|
Register |
|
On Line at:
|
WWW.UgaEd.com |
|
Fax at: |
(770)
679-5085 |
|
Phone at: |
(770)
679-5085 |
|
US Mail
at: |
|
1340
Hickory Hill Dr. |
|
Watkinsville, Ga 30677 |
|
|
|